Total Tests

10

Pass Rate

90%

Passed

9

Failures

1

EquipmentTestPhaseAs-FoundCriteriaResultInstrumentDate
SWG-MV-01Insulation ResistanceA-G12,500 MΩ≥ 5,000 MΩPASSMEG-2024-12342026-04-10
SWG-MV-01Insulation ResistanceB-G11,800 MΩ≥ 5,000 MΩPASSMEG-2024-12342026-04-10
SWG-MV-01Insulation ResistanceC-G3,200 MΩ≥ 5,000 MΩFAILMEG-2024-12342026-04-10
SWG-MV-01Contact ResistanceA85 μΩ< 150 μΩPASSMEG-2023-56782026-04-10
SWG-MV-01Contact ResistanceB92 μΩ< 150 μΩPASSMEG-2023-56782026-04-10
SWG-MV-01Contact ResistanceC88 μΩ< 150 μΩPASSMEG-2023-56782026-04-10
XFMR-1ATurns RatioA28.75:1±0.5% of 28.75PASSMEG-2023-78902026-04-08
XFMR-1AWinding ResistanceA0.245 Ω±2% balancePASSMEG-2023-56782026-04-08
RLY-SEL-751A51P Pickup—5.15A5.0A ±5%PASSMEG-2022-90122026-04-11
BAT-DC-01Cell Float VoltageCell 12.26V2.25V ±0.03VPASSDMM-0012026-04-09

AI Anomaly Detection & Trending

SWG-MV-01 — Insulation Resistance (Phase C-G)

NETA Table 100.1 minimum: 5,000 MO for 15kV class

Anomaly Detected
18.5k
2023-04
16.2k
2023-10
14.1k
2024-04
10.8k
2024-10
7.2k
2025-04
5.1k
2025-11
3.2k
2026-04
Measured Below NETA min NETA Table 100.1 minimum

AI Trend Analysis — CRITICAL

Phase C-G insulation resistance has been steadily degrading over 7 test cycles (36 months). Rate of decline: -4,300 MO/year. Current value (3,200 MO) is 36% below the NETA Table 100.1 minimum of 5,000 MO for 15kV class equipment. At current degradation rate, insulation resistance would reach zero in approximately 9 months (Jan 2027).

Recommendation: Investigate Phase C bus insulation for moisture ingress, contamination, or physical damage. Do not energize until root cause is identified and corrected. Retest after remediation.

Fleet Comparison — Contact Resistance (BKR-1 Primary Contacts)

85 uO

Phase A — 23rd percentile

Better than 77% of fleet

92 uO

Phase B — 31st percentile

Better than 69% of fleet

88 uO

Phase C — 27th percentile

Better than 73% of fleet

Fleet baseline: 120 uO average across 47 similar MV breakers. Manufacturer max: 150 uO. Phase balance: 8.2% (acceptable, <10%).